Viessmann · Boiler troubleshooting
Heating circuit pump behaviour in heating programs
What is going on
In the reduced or frost-protection programs the heating circuit pumps are switched off when outdoor temperature rises more than 1 °C (1.8 °F) above desired room temperature. In the other program they only run when there is a risk of freezing, and the mixing valve stays closed (goes to control mode when freezing is a risk). Heating circuit 1 or 2 is switched off if current room temperature exceeds the desired room temperature by 3 °C (5.4 °F). The heating circuit 2 pump is off when 20 minutes of Close mixing valve pulses are reached. Pump behaviour can be changed by the installer in the component settings.
Applies to: Vitotronic 200 Model KW2 heating circuit pumps
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 200 Model KW2 service instructions, p. 100. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.