Viessmann · Boiler troubleshooting

Heating circuit pump behaviour in heating programs

Vitotronic 200

What is going on

In the reduced or frost-protection programs the heating circuit pumps are switched off when outdoor temperature rises more than 1 °C (1.8 °F) above desired room temperature. In the other program they only run when there is a risk of freezing, and the mixing valve stays closed (goes to control mode when freezing is a risk). Heating circuit 1 or 2 is switched off if current room temperature exceeds the desired room temperature by 3 °C (5.4 °F). The heating circuit 2 pump is off when 20 minutes of Close mixing valve pulses are reached. Pump behaviour can be changed by the installer in the component settings.

Applies to: Vitotronic 200 Model KW2 heating circuit pumps

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 200 Model KW2 service instructions, p. 100. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.