Viessmann · Boiler troubleshooting

Set LON participant numbers and functions

Vitodens 200-W B2HA

What is going on

Sets LON participant numbers and related functions through coding level 2 for a single boiler with Vitotronic 200-H, HK1B mixing valve control and Vitocom LON communication module. The LON communication module accessory must be fitted.

Check in this order

  1. Fit the LON communication module (accessory) and follow its installation instructions.
  2. Set each participant number once only. The same number cannot be used twice on one LON system.
  3. Program only one Vitotronic as fault manager (79:1). All others use 79:0.
  4. Set time and outside temperature transmission codes as per the LON table.
  5. Allow several minutes for LON data transfer before judging the result.

Applies to: Vitodens 200-W B2HA 80-100 single boiler LON system

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HA service instructions, p. 42. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.