Set LON participant numbers and functions
What is going on
Sets LON participant numbers and related functions through coding level 2 for a single boiler with Vitotronic 200-H, HK1B mixing valve control and Vitocom LON communication module. The LON communication module accessory must be fitted.
Check in this order
- Fit the LON communication module (accessory) and follow its installation instructions.
- Set each participant number once only. The same number cannot be used twice on one LON system.
- Program only one Vitotronic as fault manager (79:1). All others use 79:0.
- Set time and outside temperature transmission codes as per the LON table.
- Allow several minutes for LON data transfer before judging the result.
Applies to: Vitodens 200-W B2HA 80-100 single boiler LON system
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA service instructions, p. 42. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.