Shut down the boiler before inspection
What is going on
Isolate power and fuel and open the boiler before any cleaning or inspection.
Check in this order
- Turn off main power to the heating system and lock it out against reactivation.
- Unplug the burner plug.
- Close the main oil or gas supply valve.
- For a gas power burner, disconnect the gas train.
- Loosen the four M12 bolts on the combustion chamber door and open the door.
- Remove the clean-out opening covers.
Applies to: All VD2 sizes 320 to 1080
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 200 VD2 Series 320 to 1080 Service Instructions, p. 9. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.