Before troubleshooting: power and wiring checks
What is going on
Basic checks before diagnosing a boiler that will not fire. Always turn off all power before servicing; the ON/OFF switch does not remove all power.
Check in this order
- Turn off all power to the boiler before servicing. Internal wiring stays powered with the switch off.
- Check single-phase supply at 120VAC (102 to 132VAC). Three-phase boilers need 208VAC (176 to 229VAC).
- Check the control's last three lockout histories (Diagnostics - Past Errors).
- Check space heating thermostat calling and contacts closed, including zone controls, with 24VAC at thermostat wire nuts to ground.
- Check DHW aquastat and BMS are calling for heat if used.
- Make sure all external limit controls are installed and closed, or temporarily jumpered for testing only.
- Make sure connectors to the control module and harness are fully plugged in.
- Confirm gas pressure is as specified on page 47 and no gas pressure switch is tripped.
Applies to: SVF 1500-3000 Series 1 boiler
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SVF Series 1 boiler manual, p. 99-100. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.