Weil-McLain · Boiler troubleshooting

Before troubleshooting: power and wiring checks

SVF Series 1

What is going on

Basic checks before diagnosing a boiler that will not fire. Always turn off all power before servicing; the ON/OFF switch does not remove all power.

Check in this order

  1. Turn off all power to the boiler before servicing. Internal wiring stays powered with the switch off.
  2. Check single-phase supply at 120VAC (102 to 132VAC). Three-phase boilers need 208VAC (176 to 229VAC).
  3. Check the control's last three lockout histories (Diagnostics - Past Errors).
  4. Check space heating thermostat calling and contacts closed, including zone controls, with 24VAC at thermostat wire nuts to ground.
  5. Check DHW aquastat and BMS are calling for heat if used.
  6. Make sure all external limit controls are installed and closed, or temporarily jumpered for testing only.
  7. Make sure connectors to the control module and harness are fully plugged in.
  8. Confirm gas pressure is as specified on page 47 and no gas pressure switch is tripped.

Applies to: SVF 1500-3000 Series 1 boiler

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SVF Series 1 boiler manual, p. 99-100. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.