Viessmann · Boiler troubleshooting
AUX 0-10 VDC input wiring
What is going on
The 0-10 VDC input lets a BMS set the common supply set point. The control runs to the higher of this set point and the outdoor reset set point.
Check in this order
- Wire the BMS or 0-10 VDC device output to the AUX terminals.
- Connect the negative lead to the left AUX terminal and the positive lead to the right terminal.
- Use low-voltage wiring and keep it away from 120/240 VAC conductors.
Applies to: AUX terminals, 0-10 VDC
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 300 Cascade Control technical, installation and configuration manual, p. 12. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.