Viessmann · Boiler troubleshooting

Inspect and replace burner gasket and cylinder

Vitodens 100-W, WB1B

What is going on

Check the burner gasket and burner cylinder for damage. Replace the cylinder assembly if damaged.

Likely causes

  • Damaged burner gasket
  • Damaged burner cylinder assembly

Check in this order

  1. Remove the electrode block.
  2. Remove the three Torx screws and the thermal insulation ring.
  3. Remove the four Torx screws, the burner cylinder assembly and the assembly gasket.
  4. Fit the new cylinder assembly and new gasket, and tighten to 3.5 Nm (31 lb.in.) with a calibrated torque wrench.
  5. Refit the thermal insulation ring.
  6. Refit the electrode block and tighten to 3.5 Nm (31 lb.in.) with a calibrated torque wrench.

Applies to: Vitodens 100-W, WB1B

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 100-W, WB1B installation and service instructions, p. 68. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.