Weil-McLain · Boiler troubleshooting

Test field-installed controls

EGPEG

What is going on

Checks any additional low water cutoff, high limit or other control added to the boiler.

Check in this order

  1. Test each field-installed control as outlined by its manufacturer.
  2. Confirm the burners are operating and go off when each control is tested.
  3. Restore each control and confirm the burners reignite.

Applies to: EG and PEG Series 7 boilers with added controls

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain EG/PEG Series 7 Boiler Manual, p. 65. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.