Chemical cleaning of the domestic hot water circuit

ECO Tec Series 3

What is going on

Connect a circulating pump with chemical to the DHW cold inlet and DHW outlet, clean, rinse and restore the boiler.

Check in this order

  1. Shut down the boiler follow the 'To Turn Off Gas to Appliance' instructions and close the boiler manual gas valve.
  2. Close the cold water inlet valve ahead of the boiler inlet.
  3. Release residual pressure by opening a hot tap downstream of the boiler, then close the DHW outlet valve.
  4. Connect the cleaning pump hoses to the cold water inlet and the DHW outlet.
  5. Fill the pump tank with NSF-approved descaling chemical.
  6. Circulate the fluid through the DHW circuit. Reverse flow by moving the pump to the DHW outlet hose if needed.
  7. At the end of the cycle, empty the pump and dispose of the spent solution.
  8. Fill the pump with water and flush out the chemical; repeat if necessary.
  9. Disconnect the pump hoses and reopen the cold water inlet valve.
  10. Restore electrical power and turn the boiler on.
  11. Check boiler operation and DHW production.

Applies to: 80/110/150/199 Series 3

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec series 3 boiler manual, p. 155. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.