Weil-McLain · Boiler troubleshooting
Install the Weil-McLain sidewall vent/air cap
What is going on
Mark, cut and mount the outside and inside wall plates first, then fit the termination, then run piping to the boiler.
Check in this order
- Set the template supplied with the kit on the outside wall. Level it with a spirit level so the vent and air openings sit side by side.
- Mark the four mounting holes, the vent opening and the air opening. Check for obstructions first.
- Cut the wall openings. Drill small centering holes first, then drill the large openings from both inside and outside. A single rectangular cutout may replace two holes.
- Drill the outside plate holes, install the outside plate and temporarily mount the termination.
- Cut the vent pipe so it fully enters the termination socket. Cut the air pipe so it butts against the stops inside the termination.
- On Ultra-230 installs using 3-inch vent pipe with a 4-inch termination, enlarge the vent pipe to 4 inch before it passes through the wall.
- Slide the pipes through the opening and position the inside plate so the pipes slope down toward the boiler at 1/4 inch per foot. Mark, remove the pipes, drill and mount the inside plate.
- Test fit the termination. Apply silicone RTV sealant inside the vent termination, slide it onto the vent pipe and rotate slightly to spread the sealant.
- Secure the termination with four #10 x 1/2 inch sheet metal screws and lock washers.
Applies to: Ultra boilers using the Weil-McLain sidewall termination plate
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Ultra Series 4 boiler manual, p. 70. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.