Viessmann · Boiler troubleshooting
Check water fill pressure and safety devices
What is going on
Perform these checks on a cold system. A low fill pressure usually means water loss from a leak, and all leaks must be fixed.
Likely causes
- Water loss through leakage, shown by low fill pressure
Check in this order
- Check the pressure gauge, air vent and pressure relief valve.
- Confirm the pressure relief valve does not leak and operates to its manufacturer's data.
- Check system water pressure in the diaphragm expansion tank, low water cut-offs, pumps and pressure relief valve.
- Confirm the usual cold fill pressure is 12 to 15 psig.
- Flush float-type low water cut-offs if used.
- Refer to the auto fill valve instructions and local backflow rules.
- Lubricate oil-lubricated pumps if used.
- Check motorized zone valves per their maintenance instructions.
- On an older non-diaphragm tank, confirm the correct water level (about one-half full).
Applies to: All VD2 sizes 320 to 1080
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 200 VD2 Series 320 to 1080 Service Instructions, p. 11. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.