Check water fill pressure and safety devices

Vitorond 200 VD2

What is going on

Perform these checks on a cold system. A low fill pressure usually means water loss from a leak, and all leaks must be fixed.

Likely causes

  • Water loss through leakage, shown by low fill pressure

Check in this order

  1. Check the pressure gauge, air vent and pressure relief valve.
  2. Confirm the pressure relief valve does not leak and operates to its manufacturer's data.
  3. Check system water pressure in the diaphragm expansion tank, low water cut-offs, pumps and pressure relief valve.
  4. Confirm the usual cold fill pressure is 12 to 15 psig.
  5. Flush float-type low water cut-offs if used.
  6. Refer to the auto fill valve instructions and local backflow rules.
  7. Lubricate oil-lubricated pumps if used.
  8. Check motorized zone valves per their maintenance instructions.
  9. On an older non-diaphragm tank, confirm the correct water level (about one-half full).

Applies to: All VD2 sizes 320 to 1080

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 200 VD2 Series 320 to 1080 Service Instructions, p. 11. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.