Weil-McLain · Boiler troubleshooting

Locating the direct vent air inlet termination

Ultra Series 4

What is going on

Pick the air inlet location so it is clear of debris, plants and wind eddies, and is far enough from other vents and openings.

Likely causes

  • Air inlet blocked by plants, leaves, snow or sediment
  • Air inlet placed where wind eddies or exhaust from other appliances can recirculate into it
  • Air inlet too close to another appliance or building vent outlet

Check in this order

  1. Use a down-turned air inlet elbow, with the left-side layout unless clearance to grade or snow line fails, then use the raised right-side layout.
  2. Keep the air inlet at least 12 inches below and at least 12 inches horizontally from any appliance or building vent outlet.
  3. Keep the air inlet away from inside building corners, window wells, stairwells, alcoves, courtyards and recessed areas.
  4. Keep the termination away from plants that could grow into it.
  5. Protect the termination from stones, balls and leaf or sediment buildup.
  6. Secure air pipe runs up the wall with braces no more than 24 inches apart.
  7. For Canadian installs, meet CSA B149.1 or B149.2 clearances.

Applies to: Ultra boilers, direct vent vertical vent / sidewall air

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Ultra Series 4 boiler manual, p. 80. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.