Weil-McLain · Boiler troubleshooting
Check the expansion tank
What is going on
Check tank type, fill and sizing. A relief valve that weeps often points to a waterlogged or undersized tank.
Likely causes
- Waterlogged closed-type tank
- Undersized tank
- Diaphragm or bladder membrane damaged
Check in this order
- Identify the tank type open, closed, diaphragm or bladder
- For a closed-type tank, confirm a tank fitting such as a B&G Airtrol is installed; if not, install one
- Check the fill level per the fitting manufacturer's instructions
- If fill level is correct, check tank size against the manufacturer's instructions and replace with a larger tank if needed
- For a diaphragm or bladder tank, confirm it is large enough for the system; add tanks if too small
- If the tank size is adequate, remove it and check charge pressure; if it will not hold pressure, the membrane is damaged and the tank must be replaced
- Do not use automatic air vents on systems with closed-type tanks
Applies to: SVF 500/600 Series 1 boiler
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF 500/600 Series 1 boiler manual, p. 108. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.