Weil-McLain · Boiler troubleshooting

Check the expansion tank

SVF 500/600 Series 1

What is going on

Check tank type, fill and sizing. A relief valve that weeps often points to a waterlogged or undersized tank.

Likely causes

  • Waterlogged closed-type tank
  • Undersized tank
  • Diaphragm or bladder membrane damaged

Check in this order

  1. Identify the tank type open, closed, diaphragm or bladder
  2. For a closed-type tank, confirm a tank fitting such as a B&G Airtrol is installed; if not, install one
  3. Check the fill level per the fitting manufacturer's instructions
  4. If fill level is correct, check tank size against the manufacturer's instructions and replace with a larger tank if needed
  5. For a diaphragm or bladder tank, confirm it is large enough for the system; add tanks if too small
  6. If the tank size is adequate, remove it and check charge pressure; if it will not hold pressure, the membrane is damaged and the tank must be replaced
  7. Do not use automatic air vents on systems with closed-type tanks

Applies to: SVF 500/600 Series 1 boiler

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF 500/600 Series 1 boiler manual, p. 108. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.