Weil-McLain · Boiler troubleshooting

System supply and return sensor installation

Evergreen Series 2

What is going on

Strap-on sensors on system supply and return piping. The control compares return temperature to supply temperature.

Check in this order

  1. Attach one strap-on sensor to the system supply piping and one to the return piping.
  2. For piping over 5 inch diameter or nonmetallic piping, use immersion sensors for faster response.
  3. Place the supply sensor at least six pipe diameters downstream of the boiler connection, but no more than 3 feet.
  4. Wire the return sensor to J19 pins 1 and 2 and the supply sensor to J19 pins 3 and 4.

Applies to: Evergreen 110/155/220/299/300/399

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 50. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.