Connect gas supply piping to boiler

ECO Tec Series 3

What is going on

Gas connection is ½ in. NPT male on top of the boiler. Installer supplies the shut-off valve and fittings.

Check in this order

  1. Use a pipe wrench on the gas line at the top of the boiler while tightening the gas line assembly to the boiler connection.
  2. Use two wrenches when tightening gas piping at the boiler so the boiler gas connection does not turn.
  3. Install steel pipe fittings per Figure 74 with a manual gas shut-off valve, union, and drip leg (tee, 4 in. nipple, cap).
  4. Apply pipe dope sparingly to male threads only, and use pipe dope compatible with propane.
  5. In Canada, identify the manual gas shut-off valve.
  6. Support gas piping with hangers, not by the boiler or its accessories.
  7. Purge all air from the gas supply piping.

Applies to: ECO Tec Series 3 all models

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec series 3 condensing gas boiler boiler manual, p. 64. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.