Weil-McLain · Boiler troubleshooting
PVC exhaust transition rule
What is going on
PVC cannot be used on the exhaust directly from the boiler. The first 10 linear feet must be CPVC, then the run can change to PVC.
Check in this order
- Use CPVC for the first 10 linear feet of exhaust, including all fittings in that section.
- After 10 linear feet of CPVC, transition the exhaust pipe and fittings to PVC.
- Use the approved CPVC-to-PVC primer and cement at the transition joint.
- Use the SlimFit CPVC/PVC adapters from Figure 96 to connect the boiler connection to the plastic pipe.
Applies to: PVC/CPVC vent exhaust
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit 1000-2000 Series 2 boiler manual, p. 25. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.