Weil-McLain · Boiler troubleshooting

Lock-up gas pressure regulator when inlet can exceed 14 in W.C.

SVF 500/600 Series 1

What is going on

Protect the boiler gas valve and pressure switches from high supply pressure.

Likely causes

  • Inlet gas pressure can rise above 14 in W.C.

Check in this order

  1. If inlet pressure can exceed 14 in W.C. at any time, install a 100% lock-up gas pressure regulator per ANSI Z21.80 in the gas supply line.
  2. Expect lock-up regulator pressure spikes of 5 in W.C. or 150% of setting, whichever is greater.
  3. With the boiler at minimum input rate, adjust the lock-up regulator so inlet pressure is below 10 in W.C. This leaves a margin below the high gas pressure switch setting.
  4. Adjust gas pressure higher or lower as needed within the limits of the system.

Applies to: SVF 500/600 natural gas or propane supply lines

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SVF 500/600 Series 1 boiler manual, p. 62. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.