Viessmann · Boiler troubleshooting

Burner does not switch on (single-boiler)

Vitotronic 100, GC1

What is going on

Boiler is running but the burner does not fire.

Likely causes

  • Heating program 9 is set (its button is lit)
  • Vitoair draught stabilizer defective (pressure jet burner boilers only)
  • Motor-controlled flue gas damper failed (gas boilers with atmospheric burner only)
  • Fault on the control unit
  • No fuel: oil or LPG supply empty, or natural gas valve closed

Check in this order

  1. Set the rw or w heating program (see page 6 of the manual).
  2. If the Vitoair is faulty, inform the heating contractor. To run it in manual, press in rotary knob A on the motor and turn it fully beyond setting 4.
  3. If the flue gas damper has failed, inform the heating contractor. To run it in manual, press in rotary knob A on the motor and turn it fully beyond setting 4.
  4. If there is a control unit fault, consult the heating contractor. Only then turn emissions test switch S to h with the cover left open to run temporarily at constant boiler water temperature.
  5. Oil or LPG check the fuel supply and reorder if needed. Natural gas: open the gas shut-off valve or contact the gas supplier.

Applies to: Single-boiler systems

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100, GC1 operating instructions, p. 13. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.