Viessmann · Boiler troubleshooting

Checking heating water connections and flue gas for leaks

Vitocrossal 300 CA3B Dual Fuel

What is going on

Work on pressure-loaded parts only when the boiler is unpressurized. Under-pressure can damage the boiler, so drain only with open venting and a suction pump. Flue gases can contain deadly carbon monoxide.

Check in this order

  1. Make sure the boiler is unpressurized before opening any heating water connection.
  2. Empty the boiler only with open venting, using a suction pump if needed.
  3. Check the connections for control equipment and the minimum pressure monitor (low-water indicator) for leaks.
  4. Check the flue gas collector and boiler body for leaks.
  5. Confirm all flue gases are safely vented to the outdoors.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.