All brands · Boiler troubleshooting

Won't fire

What is going on

A boiler that won't fire usually has something in the chain keeping the burner from getting its go signal. In my experience it's the stat or the safety string before it's the burner itself. Start at the power, walk the sequence, and find the first thing that doesn't happen.

Likely causes

  • No power or reversed polarity at the boiler
  • Blocked vent or intake, or vent damper not rotating
  • Tripped rollout or blocked-vent switch, or open limit or operating control
  • Thermostat trouble from vibration, oxidized contacts, a broken wire or the setting
  • Low water cutoff tripped from low water or foaming, or flow switch open

Check in this order

  1. Meter at the service switch, black should be hot and white neutral
  2. Watch the start sequence and note where it stops
  3. Ohm the switches in the safety string to find the open one
  4. Inspect the flue and intake for blockage
  5. Check the vent damper actually rotates
  6. Find why a safety tripped before resetting it, and never jumper one
  7. Call a licensed tech for gas or combustion issues

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.