Measure gas static and running pressure
What is going on
Check the gas supply pressure at the gas combination valve before and during startup. Record the readings in the Maintenance Record on page 96.
Check in this order
- Remove the boiler enclosure panel as shown on page 12.
- Close the field-supplied gas shut-off valve.
- Loosen the screw at inlet gas pressure port A on the gas combination valve but do not remove it. Connect the manometer.
- Open the gas shut-off valve and measure the static pressure. Maximum is 14 in. w.c. for NG and 14 in. w.c. for LPG.
- Start the boiler with ON/OFF switch 8 and measure the running pressure. Use a gauge that reads at least 0.04 in. w.c. resolution.
- Record the gas type and readings. Switch the boiler off, close the gas valve, remove the manometer and retighten the port screw.
Applies to: Vitodens 200-W B2HA 45, 60
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 17. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.