Boiler control power supply, 120 VAC single-phase (VD2/VD2A/CT3)

Vitotronic 100

What is going on

Supply the control through a disconnect and overcurrent protection. The main supply must have overcurrent protection rated at most 15 A and a 2-pole disconnect. The control must be grounded, and L, N and G must not be interchanged.

Check in this order

  1. Make sure the main supply to the control has overcurrent protection rated at 15 A maximum and a 2-pole disconnect.
  2. Connect the supply wire to terminals 11, N and G on the DIN rail inside the connection enclosure.
  3. Confirm the control is grounded.
  4. Check that L, N and G are not interchanged.

Applies to: VD2, VD2A and CT3 boiler controls on 120 VAC 1PH supply

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 GC1 installation and service instructions, p. 82. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.