Provide room air openings
What is going on
Air opening rules depend on whether the Ultra is alone in the boiler room or shares the space with other gas or oil appliances.
Check in this order
- If the boiler is alone and clearances are at least the service clearances in Figure 1, no room openings are needed.
- If clearances are smaller, provide two openings. Each must have 1 sq in free area per 1,000 Btuh of boiler input.
- If other appliances share the space, size the openings for those appliances using the National Fuel Gas Code or CAN/CSA B149.1 and B149.2. The Ultra needs no added opening area because it is direct vent.
- Reinstall the boiler jacket front door after service and make sure it is secured.
Applies to: Ultra Series 4 boilers
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain Series 4 gas-fired water boiler manual, p. 6. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.