Weil-McLain · Boiler troubleshooting

Shadow boiler not showing on the multi-boiler network

Weil-McLain ECO Tec Series 3

What is going on

One ECO Tec master can run up to 8 boilers over RS485. After power-up it can take 30 seconds to 1 minute before the master sees the shadows.

Likely causes

  • Duplicate or missing shadow address
  • RS485 wiring wrong or looped back to the master
  • Communication harness not installed

Check in this order

  1. Safety first turn off power at the service switch before touching wiring. Gas-side work is for a qualified gas technician only.
  2. Wait 1 minute after power-up before calling it a fault.
  3. Give each shadow its own address from 2 to 8. No two boilers can share an address.
  4. The RS485 harness kit (P/N 383700272) plugs into J12.
  5. Wire master A2/B2/GND to shadow 2 A2/B2/GND, then shadow 2 A3/B3/GND to shadow 3, and so on.
  6. Do not run the last shadow back to the master's A3/B3/GND. Ground the drain wire at the last boiler.
  7. With Unity boilers on the network, the ECO Tec must be the master.
  8. A boiler that drops off and comes back is put back where it was by the master on its own.

Applies to: ECO Tec 80, 110, 150, 199 Series 3 (heat only)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain ECO Tec Series 3 Advanced Manual 550-100-600/1025, sec. Multiple boilers / control features, p.4; Multiple boiler communication wiring, p.17-18. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.