Viessmann · Boiler troubleshooting

Multi-circuit layout with mixing valves and one unmixed circuit

Vitodens 200-W B2HB

What is going on

Layout for a boiler with DHW tank, low-loss header, several heating circuits with mixing valves and one circuit without a mixing valve. Viessmann recommends contacting the local sales representative for design help. The Vitotronic 200-H HK1B mixing valve control with LON module can replace the accessory kit and Vitocontrol.

Check in this order

  1. Locate the expansion tank so it can be reached and serviced, as the diagram shows.
  2. Pipe pumps C and K so they pump into the boiler, as illustrated.
  3. Fit the Viessmann temperature sensor on the low-loss header.
  4. Fit mixing valve temperature sensors on each mixing circuit.
  5. Set the heating circuit pump 28/20 function through coding address 53.

Applies to: Vitodens 200-W B2HB with Vitotronic 200, HO1B outdoor reset control, system layout 9

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HB 19 to 35, 68 to 125 Installation Instructions, p. 41. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.