Viessmann · Boiler troubleshooting

Checking the plate heat exchanger

Vitodens 222-F

What is going on

Drain the boiler on the heating water and DHW sides first. Small amounts of water may trickle out during removal.

Check in this order

  1. Shut off and drain the boiler on the heating water and DHW sides.
  2. Release the side closures and pivot the control unit forward.
  3. Remove the siphon (see p. 25).
  4. Push insulating mat A upwards and remove it.
  5. Undo two screws B and pull plate heat exchanger C out to the front.
  6. Check the heating water and DHW connections for contamination and scaling. Replace the plate heat exchanger if required.
  7. Install in reverse order with new gaskets.

Applies to: Vitodens 222-F B2TB

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 222-F B2TB service instructions, p. 85. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.