Viessmann · Boiler troubleshooting
Fault lamp on control unit with blinking burner control display
What is going on
Fault after start-up or during gas supply problems. Reset the burner control unit and check the gas supply.
Likely causes
- Insufficient gas in the gas pipe during initial start-up
- Supply side of combination gas valve blocked after gas pipe work
Check in this order
- Press reset button R on the burner control unit.
- If the fault continues, check the supply side of the combination gas valve for blockage from gas pipe work.
- On initial start-up, ventilate the gas line again and reset the burner control unit.
- Allow 3 min delay before the burner starts.
Applies to: CA3B boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 service instructions, p. 33. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.