System Layout 6: B1KE with closely spaced tees

Vitodens 100-W B1HE/B1KE

What is going on

B1KE boiler with closely spaced tees and one heating circuit. A low-loss header is strongly preferred.

Check in this order

  1. Space the tees at 4 times the pipe diameter or 12 in (305 mm).
  2. Connect heating circuit pump P2 and the outdoor temperature sensor.
  3. Install a DHW tempering valve and sediment filter (field supplied).

Applies to: B1KE 120, 199 with closely spaced tees

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 100-W B1HE/B1KE Combi Installation and Service Instructions, p. 38. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.