System Layout 6: B1KE with closely spaced tees
What is going on
B1KE boiler with closely spaced tees and one heating circuit. A low-loss header is strongly preferred.
Check in this order
- Space the tees at 4 times the pipe diameter or 12 in (305 mm).
- Connect heating circuit pump P2 and the outdoor temperature sensor.
- Install a DHW tempering valve and sediment filter (field supplied).
Applies to: B1KE 120, 199 with closely spaced tees
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 100-W B1HE/B1KE Combi Installation and Service Instructions, p. 38. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.