Viessmann · Boiler troubleshooting
Actuator test
What is going on
Each actuator can be switched on separately to check it. Before an actuator is selected, all actuators are switched off. Tests run at the relay outputs and depend on system equipment level and control unit configuration. Mixing valve tests need the supply temperature to rise when the valve opens.
Likely causes
- Supply temperature falls when the valve opens: motor turning in the wrong direction or valve set fitted incorrectly
Check in this order
- From the home screen tap Menu, then Service.
- Enter the viservice password.
- Tap Actuator test.
- Select the actuator to test, for example DHW tank primary pump, DHW circ pump, Htg circ pump HC2 or HC3, Mixing valve HC2 or HC3, central fault message, EA1 output 1, AM1 output 1 or 2, or solar circuit pump.
- Confirm the actuator switches ON or moves to Open/Close.
- For a mixing valve, confirm the supply temperature rises on opening; if it drops, check motor rotation and valve installation against the mixing valve instructions.
Applies to: Actuator test of pumps, mixing valves, relays and solar outputs
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Dual Fuel Service Instructions, p. 118. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.