Weil-McLain · Boiler troubleshooting
Check ignition safety shutoff device
What is going on
Confirms the boiler locks out when ignition fails.
Likely causes
- Manual gas valve closed (test condition)
Check in this order
- Turn the boiler off and close the manual gas valve on the gas line.
- Turn the boiler on. It will attempt ignition but not light.
- Wait for lockout. Display shows a red banner and Ignition Fault 1.
- Clear the lockout by selecting Manual Reset on the Homeowner screen.
- Open the manual gas valve to restore fuel.
Applies to: ECO Tec Series 3 80/110/150/199
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 136. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.