Viessmann · Boiler troubleshooting

Checking and cleaning the burner tube and gauze

Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

What is going on

Cleaning or replacing the burner gauze and inspecting the insulation ring.

Likely causes

  • Contamination of the burner tube can cause malfunctions.
  • Scratches in the combustion chamber can cause corrosion.

Check in this order

  1. Dismantle the burner first (see page 69).
  2. Undo the 6 screws from the insulation ring (torque 13 lb.in / 1.5 Nm on refit) and remove the ring.
  3. Unscrew the burner gauze assembly. Vacuum it or replace it (torque 7.5 lb.ft / 10 Nm on refit).
  4. Replace all gaskets and reassemble in reverse order (torque 7.5 lb.ft / 10 Nm).
  5. Keep the combustion chamber free of insulation fibres and do not let tools fall in.
  6. Close the gas shut-off valve before working and only work on the burner when the system is cold.

Applies to: Vitocrossal 300 CA3B Dual Fuel burner tube

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 Service Instructions, p. 71. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.