Viessmann · Boiler troubleshooting
Checking and cleaning the burner tube and gauze
What is going on
Cleaning or replacing the burner gauze and inspecting the insulation ring.
Likely causes
- Contamination of the burner tube can cause malfunctions.
- Scratches in the combustion chamber can cause corrosion.
Check in this order
- Dismantle the burner first (see page 69).
- Undo the 6 screws from the insulation ring (torque 13 lb.in / 1.5 Nm on refit) and remove the ring.
- Unscrew the burner gauze assembly. Vacuum it or replace it (torque 7.5 lb.ft / 10 Nm on refit).
- Replace all gaskets and reassemble in reverse order (torque 7.5 lb.ft / 10 Nm).
- Keep the combustion chamber free of insulation fibres and do not let tools fall in.
- Close the gas shut-off valve before working and only work on the burner when the system is cold.
Applies to: Vitocrossal 300 CA3B Dual Fuel burner tube
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 Service Instructions, p. 71. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.