Monthly condensate drain and trap check
What is going on
With the boiler running, flue gas must not come from the condensate drain or tee. A dry trap lets flue products into the boiler room.
Likely causes
- Dry condensate trap (not enough condensate from the Ultra vent)
- Obstructed condensate drain line
Check in this order
- While the boiler runs, hold a hand near the discharge end of the condensate drain tubing and the open top of the condensate tee. Check for flue gas escaping.
- If flue gas escapes, the trap is dry. Refill the trap using the procedure below.
- To check for an obstruction, slowly pour water into the top of the PVC tee on the boiler side. Water should run out the end of the drain line.
- If water does not run out, call a qualified service technician to clean or replace the condensate drain line.
- To refill the trap, temporarily plug the drain line end. Slowly pour water into the 1/2 inch plastic tee on the boiler right side until it fills the drain line and overflows into the trap tubing.
- Stop when water reaches the top of the 1/2 inch tee. Remove the temporary plug from the drain line end.
- If the trap keeps running dry, call a qualified service technician to inspect the boiler and condensate line.
Applies to: Ultra Series 4 condensate drain line, condensate tee and trap
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Ultra Series 4 user's information manual, p. 7. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.