Checking flue gas leakage at full load

Vitocrossal 300 CA3B Dual Fuel

What is going on

Check the flue gas collector and boiler body for leakage with the boiler at full load. Flue gas may contain carbon monoxide, so all flue gases must be vented outdoors.

Check in this order

  1. Run the boiler at full load operation.
  2. Check the gaskets with a dew point hygrometer. Remove thermal insulation parts if needed.
  3. Look for condensed water on the outside of the flue gas collector or on the insulation. Wet spots indicate a leak.
  4. Check the flue gas collector and boiler body for leakage.
  5. Confirm all flue gases are safely vented to the outdoors.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.