Understanding the Vent Installation Detector (VID)
What is going on
The VID only confirms the pipe is inserted at least 2-3/4 in into the collar. It is not a gas leak or CO detector and will not catch joints that come apart further along the vent run.
Likely causes
- Joints separating further along the vent run
- Blocked vent
- Sensor failure or switch sticking
Check in this order
- Inspect vent joints regularly because the VID will not detect separated joints or leaks.
- Use a CO detector as required by local code.
- Do not rely on the VID to catch vent movement after installation.
Applies to: NCB700 series
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NCB700 installation and operation manual, p. 62-64. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.