Viessmann · Boiler troubleshooting
Changing the mixing valve motor rotation direction
What is going on
Reverses the open and closed direction of the mixing valve motor.
Check in this order
- Remove the motor cover.
- Reinsert the 3-pole plug A turned by 180 degrees.
- Run the relay test to confirm the valve moves to Open and Closed.
Applies to: Mixing valve motor
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 200-H Installation and Service Instructions, p. 40. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.