Viessmann · Boiler troubleshooting
Change filter in combustion air filter box (room air independent operation)
What is going on
Change the filter in the combustion air filter box for room air independent operation. After installing the new filter with the filter monitoring kit, cycle the boiler power to reset the filter message.
Likely causes
- Filter reached end of service life
Check in this order
- Release the latches on the end of the combustion air filter box.
- Remove the filter box cover.
- Release the filter clamp on the base of the filter.
- Remove the filter.
- Install the new filter in reverse order.
- If using the filter monitoring kit, cycle the boiler power to reset the P.36 message.
Applies to: Vitocrossal 200 CI2 room air independent operation
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CI2 Service Instructions, p. 35. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.