Viessmann · Boiler troubleshooting
Check expansion tank and system water pressure
What is going on
Check the cold-system fill pressure, the diaphragm expansion tank pre-charge and the safety header. Do all checks on a cold system.
Likely causes
- Low fill pressure usually means water is leaking from the system.
- Expansion tank inlet pressure below static pressure.
Check in this order
- Use a cold system only and follow the expansion tank maker's instructions.
- Confirm the cold fill pressure is 12 to 15 psig. Correct any leaks.
- Confirm the safety header pressure gauge, air vent and relief valve operate, and that the relief valve does not leak.
- To re-charge the expansion tank, drain the system or close the tank cap valve and bleed the pressure to 0 on the gauge.
- If the tank inlet pressure is below static pressure, add nitrogen until it is 0.1 to 0.2 bar (1.5 to 3 psig) above static pressure.
- Top up with water until the cold fill pressure is 0.1 to 0.2 bar (1.5 to 3 psig) above the tank inlet pressure.
- Keep maximum operating pressure at or below 5 bar (75 psig).
- Flush float-type low water cut-offs if used.
- For an older non-diaphragm tank, check the water level is approximately half full.
Applies to: Hydronic system pressure
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 200 VD2A service instructions, p. 12. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.