Viessmann · Boiler troubleshooting

Check expansion tank and system water pressure

Vitorond 200 VD2A

What is going on

Check the cold-system fill pressure, the diaphragm expansion tank pre-charge and the safety header. Do all checks on a cold system.

Likely causes

  • Low fill pressure usually means water is leaking from the system.
  • Expansion tank inlet pressure below static pressure.

Check in this order

  1. Use a cold system only and follow the expansion tank maker's instructions.
  2. Confirm the cold fill pressure is 12 to 15 psig. Correct any leaks.
  3. Confirm the safety header pressure gauge, air vent and relief valve operate, and that the relief valve does not leak.
  4. To re-charge the expansion tank, drain the system or close the tank cap valve and bleed the pressure to 0 on the gauge.
  5. If the tank inlet pressure is below static pressure, add nitrogen until it is 0.1 to 0.2 bar (1.5 to 3 psig) above static pressure.
  6. Top up with water until the cold fill pressure is 0.1 to 0.2 bar (1.5 to 3 psig) above the tank inlet pressure.
  7. Keep maximum operating pressure at or below 5 bar (75 psig).
  8. Flush float-type low water cut-offs if used.
  9. For an older non-diaphragm tank, check the water level is approximately half full.

Applies to: Hydronic system pressure

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 200 VD2A service instructions, p. 12. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.