Viessmann · Boiler troubleshooting
Pump outputs not powered
What is going on
The unit has power, but the space heating or DHW pump outputs stay off.
Likely causes
- Blown F2 fuse
- No space heating or DHW call present
- No 120VAC signal from the boiler at the WB1 input
- Loose terminal connection
- Faulty RT/DHW interconnection between Versatronik 10.WB1 and boiler
Check in this order
- Check the F2 fuse.
- Confirm a space heating or DHW call is present.
- Confirm 120VAC is present at the WB1 input from the boiler.
- Verify the terminal connections.
- Check the RT/DHW interconnections between the Versatronik 10.WB1 and the boiler.
Applies to: Viessmann Vitodens 100-W, WB1A and WB1B with Versatronik 10.WB1
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 10.WB1 installation and operating manual, p. 25. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.