Sidewall air inlet location (vertical vent / sidewall air)

ECO Tec Series 3

What is going on

The air inlet is part of a direct vent connection, not a forced air intake. It must be placed to avoid obstructions, wind eddies and recirculation from other appliance exhausts.

Check in this order

  1. Use the air inlet elbow configuration that keeps required clearance to grade and snow line.
  2. Keep the air inlet at least 12 in below and 12 in horizontally from any appliance or building vent outlet.
  3. Keep adjacent air inlets for multiple boilers at least 6 in apart.
  4. Keep air inlet clear of plants and obstructions; avoid building corners, window wells, stairwells and alcoves.
  5. If the air pipe runs up the wall, brace it with braces no more than 24 in apart.
  6. Seal exterior wall openings with exterior caulk and use metal plates at inside and outside penetrations.

Applies to: Vertical vent / sidewall air direct vent

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec Series 3 Boiler Manual, p. 44. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.