Viessmann · Boiler troubleshooting

Check supply, tank or room temperature sensor (NTC)

Vitotronic 300

What is going on

Test an NTC sensor against its resistance curve. The room temperature sensor is wired to terminals 3 and 4 in the Vitotrol 300. The supply sensor can be used as a contact or an immersion sensor. The sensors are Viessmann NTC 10 kOhm (blue ID label). The resistance curve values are not legible in the extracted pages.

Likely causes

  • Sensor resistance far from the curve
  • Damaged or poorly installed sensor

Check in this order

  1. Pull the corresponding plug.
  2. Measure the sensor resistance and compare it with the curve.
  3. If the deviation is severe, check the installation.
  4. Replace the sensor if required.

Applies to: Supply, tank and room temperature sensors, Vitotronic 300 GW6B

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300, GW6B installation and service instructions, p. 121. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.