Install supply to return bypass on large water content systems
What is going on
Needed on systems with more than about 1 US gal (3.8 L) of water per 13,000 Btu/h of boiler input, such as older gravity systems with large free-standing radiators. Prevents flue gas condensation in the heat exchanger and vent. Viessmann recommends a bypass on all cast iron boilers.
Check in this order
- Calculate system water volume against boiler input.
- Run a bypass line from the supply pipe to the return pipe.
- Install the bypass on any system where it is wanted as a precaution.
Applies to: VR1 22 to 33, 91 to 140
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 100 installation and service manual, p. 8. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.