Weil-McLain · Boiler troubleshooting

Pilot sparks but no pilot flame

EG / PEG Series 7

What is going on

Ignition attempt where the spark is present but the pilot does not light.

Likely causes

  • Pilot valve not energized
  • Pilot gas line kinked or loose
  • No gas flowing to the pilot

Check in this order

  1. Verify the pilot valve is being energized with 24 Vac.
  2. Check that the pilot gas line is piped and routed per the manual with no kinks or loose connections.
  3. Verify gas is flowing to the pilot. If not, replace the pilot valve.

Applies to: EG water boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: EG / PEG Series 7 Boiler Manual, p. 75. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.