Viessmann · Boiler troubleshooting
Checking ignition and ionization electrodes
What is going on
Check the electrode block once the burner plate is removed.
Check in this order
- Dismount the electrode block after the burner plate is removed.
- Check the ignition electrodes and ionization electrode for damage and correct distance from the burner tube. Replace electrodes if needed.
- Install the electrode block in reverse order with new gaskets. Torque: 4.4 lb.ft (6 Nm).
Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitocrossal 300 CA3B service instructions, p. 73. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.