Change parameter A2 to allow higher exhaust temperatures
What is going on
Set A2 to b only for CPVC, listed PP or stainless steel venting. Do not do this with PVC.
Check in this order
- Remove the front panel by taking out the two screws.
- Locate the PC board on the lower left side and press the SW1 left button.
- Scroll to parameter A2 and set it to b.
- Press the SW1 left button to exit to normal operation.
- Reinstall the front panel with the two screws.
Applies to: I-Series Plus with CPVC, listed PP or stainless steel venting
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 24. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.