Viessmann · Boiler troubleshooting
Replace burner door
What is going on
Full burner door replacement, including fan, venturi and gas train removal.
Check in this order
- Loosen the retaining clamp and disconnect the combustion air flex hose. Disconnect the gas line.
- Unplug plugs 35, 36, 87, 111 and 122 from the burner control. Remove the burner control cover to reach plugs 87 and 111.
- Unplug fan plugs 100 and 100A. Disconnect pressure switch tubes APS1 from the venturi and APS2 from the burner door.
- Remove the four M8 nuts that connect the fan to the burner door. Remove the fan with venturi and gas train.
- Remove the two M6 bolts and the burner control assembly.
- Remove the ignition and ionization electrode block.
- Remove the cotter pins and hinge pins from the burner door.
- Remove the four M12 (19 mm hex) burner door bolts and washers.
- Remove the burner tube.
- Fit the new burner door. Install the door studs for the fan/venturi connection. Replace the barb fitting washer if needed.
- Tighten the fan/venturi nuts, the M12 door bolts and the M8 nuts to the torque in the torque table.
- Reassemble in reverse order and leak test the gas line.
Applies to: All CM2 models
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 40. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.