Viessmann · Boiler troubleshooting

Relay output test and sensor check

Vitotronic 100

What is going on

Tests the actuators and checks the sensors during start-up.

Check in this order

  1. Press 9 and OK together for about 2 seconds to start the relay test.
  2. Select a relay output with the up or down button and press OK to activate it.
  3. Press OK again to end the relay test.
  4. To check sensors, press the sensor button, scroll sensors with the up or down button, then press the button shown on page 89 to end.
  5. Scanning of operating status information starts, and ends when you exit (see page 97).

Applies to: Vitotronic 100 GC1 start-up, depends on installed equipment

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 GC1 installation and service instructions, p. 89. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.