Fixed high limit test, method 2 (CSD-1)
What is going on
Second way to test the fixed high limit by running the boiler at high fire with no flow. Only do this where required by law.
Check in this order
- Close the boiler valve.
- Jumper across the flow switch.
- Run the boiler at high fire. Set coding address 06 to maximum on B2TB models so the coding card runs it at high fire.
- Keep the boiler temperature rising until the fixed high limit trips.
- Once it trips, slowly open the boiler valve to cool the boiler down safely.
Applies to: Vitodens 200-W B2HA 112/150/399/530
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 200-W B2HA 112, 150, 399, 530 service instructions, p. 8. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.