Navien · Boiler troubleshooting

Convert NFC-H boiler from natural gas to propane

NFC-H

What is going on

Procedure to convert an NFC-H combi-boiler to propane, including gas valve outlet adapter removal, DIP switch setting and gas/air ratio check.

Check in this order

  1. Use only the propane conversion kit for propane conversion. Do not use the high altitude kit for natural gas when converting to propane.
  2. Shut off power and gas to the boiler before opening it.
  3. Unfasten the 4 front cover latches (2 top, 2 bottom) and remove the front cover. Set it aside safely.
  4. Locate the gas inlet pipe and the gas valve.
  5. At location A, remove the clip where the gas valve outlet adapter connects to the gas valve.
  6. At location B, remove the 4 screws with a Phillips screwdriver where the adapter attaches to the fan motor assembly. Pull the adapter away from the fan assembly.
  7. Install the conversion parts as the kit instructions show. Steps 7 and 8 are not legible in extraction; follow the kit sheet for the packing and O-ring seating.
  8. Put the gas valve outlet adapter back in its original position and install all screws. Do not overtighten.
  9. Set DIP switch 2 #1 to ON for propane or OFF for natural gas, and set switches 2 and 3 for altitude.
  10. Turn on gas and water to the boiler.
  11. Measure and adjust the gas/air ratio using a combustion analyzer (preferred) or a dual port or digital manometer.
  12. Attach the included propane conversion labels next to the rating plate. Check the conversion kit number first, because the rating plate varies by model.
  13. Check all gas connections for leaks with a gas leak detector.

Applies to: NFC-250/175H, NFC-250/200H

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NFC-H propane and high altitude conversion guide, p. 1-2. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.