Supply and return temperature sensor installation

Versatronik 300 Cascade Control

What is going on

The supply sensor goes in an immersion well. The return sensor is optional and only lets the user see the temperature difference; it has no control logic.

Check in this order

  1. Push the immersion sensor fully into the temperature well and secure it with the well clip.
  2. If there is no well, strap the sensor tight to the pipe with conductive paste and a metal strap. Do not use wire ties.
  3. Insulate over the sensor after it is secured.
  4. Wire the supply sensor to the S2 terminals inside the control.
  5. If fitting the optional return sensor, install it in a well or on the pipe and wire it to the S3 input.
  6. Keep the wiring away from high voltage and shield it as required.

Applies to: Versatronik 300 Cascade Control, supply sensor S2, return sensor S3

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 300 Cascade Control technical, installation and configuration manual, p. 9. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.