Weil-McLain · Boiler troubleshooting
Direct exhaust vertical vent termination: location and clearances
What is going on
Clearances for a vertical (roof) direct exhaust termination. The vent must end in a coupling, and all clearances must be met for the roof, walls, openings and air inlets.
Likely causes
- Termination too low on the roof or too close to a snow line
- Termination in a recessed area or near a forced air intake
Check in this order
- Terminate at least 12 in above the roof or snow line, as shown in the figure.
- Keep it at least 6 ft from adjacent walls.
- Keep it at least 5 ft below any roof overhang.
- Keep it at least 3 ft above any forced air intake within 10 ft.
- Keep it at least 48 in below or horizontally from any door, window or other gravity air inlet.
- Keep it at least 4 ft horizontally from electric meters, gas meters, regulators, relief valves or other equipment.
- End the vent piping in a coupling with a bird screen fitted.
- Keep the termination away from wind eddies, building corners, adjacent surfaces and recessed areas.
- Locate or guard the vent so condensate does not damage exterior finishes.
- Do not extend exposed vent pipe beyond the length shown in the figure.
Applies to: SF-550 and SF-750 direct exhaust, vertical termination
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit series 3 commercial gas-fired water boiler manual, p. 34-35. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.