Viessmann · Boiler troubleshooting

External mixing valve open / close contacts

Vitotronic 300-KVitotronic 200

What is going on

A closed contact opens or closes the mixing valves. The open function is assigned to the heating circuits with coding 9A (General group). The close function is assigned with coding 99 (General group). Connect both dry contacts at plug avD.

Check in this order

  1. Use potential-free dry contacts.
  2. Connect the open and close contacts at plug avD.
  3. Set coding 9A (General group) to assign the mixing-valve-open function to the heating circuits.
  4. Set coding 99 (General group) to assign the mixing-valve-close function to the heating circuits.

Applies to: Mixing valves open/close

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 200 and 300-K Installation and Service, p. 22. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.